Pro Tip: Quite a few F&G Detectors require Triad Cables

Pro Tip: Note that if you have 2oo3 Transmitter Configuration then all 3 Transmitters must go through separate JB. (Why? Because SIL loops required independent path)

Pro Tip: General Spare Capacity is 20% but if you are starting a project keep a hidden Spare of extra 20%. Since most of the time Instruments keep adding till the final stages of the project.